Run time for load |
5min 27s |
Max. Capacity Used |
100% |
Main Input Voltage |
230 V |
Other Input Voltage |
220 V, 240 V |
Main Output Voltage |
230 V |
Other Output Voltage |
220 V, 240 V |
Rated power in W |
1980 W |
Rated power in VA |
2200 VA |
Input Connection Type |
BS1363A British, IEC 320 C20, Schuko CEE 7 / EU1-16P |
Output Connection Type |
8 IEC 320 C13, 3 IEC Jumpers, 1 IEC 320 C19 |
Number of rack unit |
2U |
Cable length |
2.00 m |
Number of cables |
1 |
Battery type |
Lead-acid battery |
Provided equipment |
CD with software, Documentation CD, Installation guide, Rack mounting hardware, Rack mounting support rails, Smart UPS signalling RS-232 cable, Temperature probe, USB cable |
Batteries & Runtime |
|
Run Time |
View Runtime Graph |
Efficiency |
View Efficiency Graph |
Additional information |
Configurable for 220 : 230 or 240 nominal output voltage, Extended runtime, Battery recharge time: 3 h |
Number of battery filled slots |
0 |
Number of battery free slots |
0 |
Number of battery replacement quantity |
1 |
Battery life |
3…5 year(s) |
Replacement battery |
RBC43 |
Battery charger power |
169 W rated |
General |
|
Number of power module filled slots |
0 |
Number of power module free slots |
0 |
product web sub-family |
Network card pre-installed |
Redundant |
No |
Physical |
|
Height |
8.6 cm |
Width |
48 cm |
Depth |
68.3 cm |
Net weight |
42.22 kg |
Mounting location |
Front |
Mounting preference |
Lower |
Mounting mode |
Rack-mounted |
Two post mountable |
0 |
USB compatible |
No |
Input |
|
Input voltage limits |
151...302 V adjustable |
Network frequency |
50/60 Hz +/- 3 Hz auto-sensing |
Output |
|
Maximum configurable power in VA |
2200 VA |
Maximum configurable power in W |
1980 W |
Transfer time |
4 ms typical : 8 ms maximum |
UPS type |
Line interactive |
Wave type |
Sine wave |
Output frequency |
50/60 Hz +/- 3 Hz sync to mains |
Conformance |
|
product certifications |
CE, EAC, IRAM, RCM, VDE |
Marking |
GS Mark |
Standards |
EN/IEC 62040-1:2019/A11:2021, EN/IEC 62040-2:2006/AC:2006, EN/IEC 62040-2:2018 |
Environmental |
|
Acoustic level |
55 dBA |
heat dissipation |
215 Btu/h |
Operating altitude |
0...10000 ft |
Ambient air temperature for operation |
0…40 °C |
Ambient air temperature for storage |
-15…45 °C |
Storage altitude |
0.00…15240.00 m |
Relative humidity |
0…95 % |
Storage Relative Humidity |
0…95 % |
Communications & Management |
|
control panel |
Multifunction LCD status and control console |
Emergency power off |
Optional |
Preinstalled device |
Network management card 3 with environmental monitoring |
Control panel |
LED status display with on line : on battery : replace battery and overload indicators |
Alarm |
Alarm when on battery : distinctive low battery alarm : configurable delays |
Surge Protection and Filtering |
|
Surge energy rate |
375 J |
Packing Units |
|
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
25.4 cm |
Package 1 Width |
98 cm |
Package 1 Length |
60 cm |
Package 1 Weight |
49.63 kg |
Logistical informations |
|
Country of origin |
PH |
Contractual warranty |
3 years repair or replace (excluding battery) and 2 years for battery |